DCIR vs AC Impedance vs ESR

DCIR, AC impedance and ESR can all be reported in milliohms, but the shared unit does not make the measurements interchangeable.

Start with the decision ↓

The engineering decision

Select the method from the decision being made and compare values only when excitation, time or frequency and operating conditions match.

Have these inputs ready

  • Required load or screening decision
  • Instrument excitation and reported quantity
  • Frequency or pulse sampling time
  • Cell SOC, temperature and history

Alternative methods for different measurement questions

Scroll horizontally to view the full diagram →

Alternative methods for different measurement questionsDC pulse, AC point and EIS are alternative routes, not successive test stages. Define ESR from the actual instrument mode. DC pulse; AC point; EIS sweepSelect from the engineering questionDC pulseΔV / ΔI at time tAC pointZ at one frequencyEIS sweepZ across frequenciesCompare only with matched conditions and validated correlation
DC pulse, AC point and EIS are alternative routes, not successive test stages. Define ESR from the actual instrument mode.

Separate the measurement definitions

DCIR uses a defined current step and a voltage difference at stated times. AC resistance or impedance uses a small alternating signal at a stated frequency. EIS measures complex impedance across a frequency range. For the DC pulse calculation, define discharge current as positive and use Rapp(t) = [Vbefore − V(t)] / [I(t) − Ibefore], with matched voltage and current sampling times.

ESR is ambiguous in battery work unless the instrument, circuit mode and derivation are stated. Replace the shorthand with the actual measurement definition.

Resistance and impedance methodsScroll horizontally to compare all columns →
MethodResultSuitable starting use
DC pulseRapp(t) with the defined baseline and current signRepresentative load sag
AC pointFrequency-specific impedance resultControlled production screening
EISComplex spectrum versus frequencyCharacterization and model fitting
ESR labelInstrument-dependent simplified valueUse only with its explicit definition

Do not substitute one method without correlation

A 1 kHz value is not a substitute for a multi-second pulse result. However, the timescale study found agreement across techniques at matched observation timescales. Comparable conditions and correlation are required; there is no universal AC-to-DC conversion factor.

A fast screening method can still be valuable when the fixture and conditions are controlled and its acceptance limit has been correlated with the required performance.

References: A study of the influence of measurement timescale on internal resistance characterisation methodologies for lithium-ion cells; Comparison of Several Methods for Determining the Internal Resistance of Lithium Ion Cells

Put the definition beside the number

Record excitation amplitude, frequency or pulse time, reported impedance component, SOC, temperature, rest, fixture and calculation.

Milliohms alone are not a comparable specification.

Measurement & validation procedure

Application acceptance checklistScroll horizontally to compare all columns →
Test / reviewRecordAcceptance condition
Identify the reported quantityInstrument mode, excitation and calculationDC resistance, impedance magnitude and real component are not conflated
Control comparison conditionsSOC, temperature, rest and fixtureCompared values use matched conditions
Validate the acceptance limitScreening result versus required performanceCorrelation and allowed error are documented

Continue this engineering task

Related engineering guidance

Prepare the evidence for review

  • Instrument method and configuration
  • Raw pulse or impedance data
  • Controlled SOC and temperature record
  • Correlation to the application acceptance test
Continue to engineering review

Technical sources & claim support

References support the stated engineering principles. Worked examples use their explicitly stated assumptions.

  1. Comparison of Several Methods for Determining the Internal Resistance of Lithium Ion Cells ↗

    Sections 4–5: DC step, AC resistance, impedance spectroscopy and pulse-duration effects

    Peer-reviewed method comparison. The proposed timing and cell values are not universal acceptance requirements.

  2. A study of the influence of measurement timescale on internal resistance characterisation methodologies for lithium-ion cells ↗

    Scientific Reports 8, 21 (2018); abstract and Figure 7: comparison at matched measurement timescales

    Peer-reviewed cell study. Numerical values apply only to the tested cells, SOC, temperature and equipment.

  3. Nonlinear Electrochemical Impedance Spectroscopy for Lithium-Ion Battery Model Parameterization ↗

    Structural parameter identifiability and conclusions: nonlinear single-particle model

    Peer-reviewed primary research. Single-particle physical model; extending the identifiability lesson to other model families is an engineering inference.

Key claims and evidence
Evidence mappingScroll horizontally to compare all columns →
ClaimBasisReference
DC, AC and impedance-spectroscopy methods produce method-dependent resultsdocumentationComparison of Several Methods for Determining the Internal Resistance of Lithium Ion Cells
Using fitted impedance parameters requires checking model identifiability and application correlationworkflowengineering workflow
ESR should be replaced by the explicit instrument definition in battery specificationsworkflowengineering workflow
PROJECT ENQUIRY

Prepare your battery brief.

Start with the information you have. Your selected battery, application and service are already included.

Open as a full page ↗